You can configure the EXCCON01 converter with a network cable directly connected to a computer. First, assign an IP address in the 192.168.127.x range to your PC, then go to the converter's address in a web browser: 192.168.127.254, shown on the back of the converter itself, to access the configuration web server. The default password is "moxa".
In "serial settings", for port no. 2, set the baud rate to 38400, and the flow control to "none". For the other parameters, leave the defaults. Press submit to save and restart.
Now it's time to enter the "operating settings" menu, again for port 2. Set the "operation mode" to "TCP Client Mode". You must specify the IP address of the gateway data logger EXCGLA01 in the fields that are shown: in this case it is 192.168.0.4. The value of the TCP port must be 1000. Confirm with "submit" and then "save and restart".
Then, under Network settings, set an IP address for the converter, making it compatible with the network within which the gateway data logger is located. Also, set the subnet mask. These parameters are specified by the local network operator. Then confirm with the "submit" button.
A double beep will warn you of the reboot.