1. Check the pressure on you boiler (normal pressure is between 1-2 bar), if the pressure drops to 0 will show E118 fault code.
2. If the pressure is below 1.5 bar, you can top up by using the filling loop, in this case is an internal filling loop with green leaver. You have to pull the green leaver and hold pulling until the pressure reach 1.5 bar.
3. After the pressure reached 1.5 bar you have to release the green leaver, the valve will close automatically.
If you didn't manage to close on time and the pressure is above 2 bar don't worry, you can just bleed a radiator and then the pressure will drop automatic. If the pressure is above 3 bar, then the boiler Pressure Relief Valve (PRV) will open and will discharge the water trough PRV pipe and the pressure will drop automatic.