In this video, two identical generators operating in parallel are examined. With a load of 200 MW, the system frequency decreases to 58.5 Hz, and both generators generate 100 MW each. By adjusting the no-load speed of Generator 1 to 61.5 Hz, the system frequency increases to 59.25 Hz, with Generator 1 producing 150 MW and Generator 2 producing 50 MW. To restore the frequency to 60 Hz, the no-load speed of Generator 2 is also increased to 61.5 Hz, resulting in both generators producing 100 MW each. The video showcases the balancing act of parallel generators with droop settings