Two addressable systems polling in the dark at work. These are test beds set up for panel functionality testing.
AFP-200 with:
NBG-12LX pull station
FCM-1 control module, creates a supervised NAC essentially.
FRM-1 relay module, an SLC controlled dry contact relay
FMM-101 mini module, wired to a toggle switch
FSP-851 photo smoke
FST-851 fixed heat, 135 deg
FAPT-851 photo smoke / heat, inoperable at this time
The AFP-200 is an older CLIP panel that is compatible with FlashScan devices.
NFW2-100 (Fire-Lite MS-9200UDLS) with:
NOT-BG12LX pull station (Fire-Lite BG-12)
NC-100 control module (Fire-Lite CMF)
NC-100R relay module (Fire-Lite CRF)
NMM-101 mini module, wired to toggle switch (FIre-Lite MMF-301)
NP-100 photo smoke (Fire-Lite SD355)
NT-100 fixed heat, 135 deg (Fire-Lite H355)
NP-100 photo smoke (Fire-Lite SD355)
N-ANN-80 annunciator (Fire-Lite ANN-80)
The NFW2-100 is a rebranded Fire-Lite panel compatible with CLIP devices and Fire-Lite's LiteSpeed series devices.
The column of blinking LEDs on the left side is from the AFP-200, the taller column on the right is from the NFW2-100.
It's a common misconception that Notifier and Fire-Lite addressable devices are the same...
The Onyx (NFS) series and all the older panels (AFP series) only work with the FlashScan series devices, such as the FSP-851. Johnson Controls-branded components will work as well, but they are not listed for use with Notifier equipment...
The FireWarden (NFW) series only works with Fire-Lite's LiteSpeed devices (and their Notifier rebrands), and NOT with the FlashScan devices. This is due to the fact that the NFW series is just re-labeled Fire-Lite products.